| Product > Converter > ALP series 10K-400KVA 50Hz/60Hz/400Hz > ALP 240-320KVA |
PHASE |
3-Phase Input / 3-Phase
Output |
||
KVA |
240 |
320 |
|
Picture (click the picture to see big picture) |
|||
INPUT (RECTIFIER) Input Voltage |
208V /220V / 380V / 400V /415V /440V /460V /480V / 600V |
||
Input Range |
+ / - 20% ( > +/- 20% is available upon
request) |
||
Input Frequency |
50 / 60 Hz + / - 5Hz |
||
Power Walk In |
0% - 100% : 20 sec |
||
Efficiency |
> 98% |
||
Voltage Regulation |
+ / - 1% |
||
INVERTER |
|
||
Output Voltage |
208V /220V / 380V / 400V /415V /440V /460V , + / - 1 % |
||
Wave Form |
Sine Wave |
||
Output Power Factor |
0.8 |
||
Output Frequency (Free Running) |
50 / 60 / 400Hz + / - 0.1 Hz |
||
Phase Shift Under 100% Unbalance Load |
< 0.5° |
||
THD (Linear Load) |
< 2 % |
||
Overload |
<110% |
Continuous |
|
110 C 125% |
15 minutes |
||
125 C 150% |
10 minutes |
||
> 150% |
1 minute |
||
Efficiency (100% Load) |
95% |
95% |
|
OVERALL CHARACTERISTICS |
|||
Overall Efficiency |
93% |
93% |
|
Maximum Heat Dissipation (Kw) |
13 |
17.4 |
|
Height x Width x Depth
(mm) |
1600 x 2200 x 800 |
||
Weight (Kg, without battery) |
1950 |
2450 |
|
Audible Noise |
< 67 dBA (At 1 M) |
||
Temperature |
0 – 40℃ ( 32 – 104℉ ) |
||
Humidity |
0% - 90% (Non-Condensing) |
||
Altitude |
<1500 M Above Sea Level |
||
EN50091-1,-2 |
YES |
||
Short Circuit Pretection |
YES |
||
Lightning / EMC Filter |
MOV / Input&Output (FCC CLASS A) |
||
Galvanic Isolation |
Input&Output true Galvanic isolation |
||
LED,LCD,Buzzer |
YES |
||
Remote Control / Communication Interface |
Monitoring 1~99 UPS simultaneously /
Dry contact, RS232, RS485 |
||
| . Different specifications required are available. . All specifications mentioned above are subject to change without prior notice. |
|||