| Product > Converter > ALP series 10K-400KVA 50Hz/60Hz/400Hz > ALP 80-160KVA |
PHASE |
3-Phase Input / 3-Phase
Output |
||||
KVA |
80 |
100 |
120 |
160 |
|
Picture (click the picture to see big picture) |
|||||
INPUT (RECTIFIER) Input Voltage |
208V /220V / 380V / 400V /415V /440V /460V /480V / 600V |
||||
Input Range |
+ / - 20% ( > +/- 20% is available upon
request) |
||||
Input Frequency |
50 / 60 Hz + / - 5Hz |
||||
Power Walk In |
0% - 100% : 20 sec |
||||
Efficiency |
> 98% |
||||
Voltage Regulation |
+ / - 1% |
||||
INVERTER |
|
||||
Output Voltage |
208V /220V / 380V / 400V /415V /440V /460V, + / - 1 % |
||||
Wave Form |
Sine Wave |
||||
Output Power Factor |
0.8 |
||||
Output Frequency (Free Running) |
50 / 60 / 400Hz + / - 0.1 Hz |
||||
Phase Shift Under 100% Unbalance Load |
< 0.5° |
||||
THD (Linear Load) |
< 2 % |
||||
Overload
|
<110% |
Continuous |
|||
110 ¨C 125% |
15 minutes |
||||
125 ¨C 150% |
10 minutes |
||||
> 150% |
1 minute |
||||
Efficiency (100% Load) |
94.5% |
94.5% |
95% |
95% |
|
OVERALL CHARACTERISTICS |
|
||||
Overall Efficiency |
92.5% |
92.5% |
93% |
93% |
|
Maximum Heat Dissipation (Kw) |
4.6 |
5.4 |
6.5 |
8.7 |
|
Height x Width x Depth
(mm) |
1600 x 1100 x 800, |
||||
Weight (Kg, without battery) |
820 |
950 |
1180 |
1450 |
|
Audible Noise |
< 67 dBA (At 1 M) |
||||
Temperature |
0 – 40℃ ( 32 – 104℉ ) |
||||
Humidity |
0% - 90% (Non-Condensing) |
||||
Altitude |
<1500 M Above Sea Level |
||||
EN50091-1,-2 |
YES |
||||
Short Circuit Pretection |
YES |
||||
Lightning / EMC Filter |
MOV / Input&Output (FCC CLASS A) |
||||
Galvanic Isolation |
Input&Output true Galvanic isolation |
||||
LED,LCD,Buzzer |
YES |
||||
Remote Control / Communication Interface |
Monitoring 1~99 UPS simultaneously /
Dry contact, RS232, RS485 |
||||
| . Different specifications required are available. . All specifications mentioned above are subject to change without prior notice. |
|||||
| Copyright © 2003-2007 SOLTEC TECHNOLOGY CO., LTD. soltec@soltec.com.tw |