| 産品 > 在線式UPS > ALP ( 真正的超隔離架構:10K-400KVA ) > ALP 15-50KVA |
| PHASE |
3-Phase Input / 1-Phase
Output |
||||
| KVA |
15 |
30 |
40 |
50 |
|
| Picture (click the picture to see big picture) |
|||||
INPUT (RECTIFIER) |
|||||
| Input Voltage |
190V /208V /220V / 380V / 400V /415V /440V /480V / 600V, 3P4W or 3P3W |
||||
| Input Range |
+ / - 20% ( > +/- 20% is available upon
request) |
||||
| Input Frequency |
50 / 60 Hz + / - 5Hz |
||||
| Power Walk In |
0% - 100% : 20 sec |
||||
| Efficiency |
> 98% |
||||
| Voltage Regulation |
+ / - 1% |
||||
| BATTERY |
|
||||
| Battery Type / Pcs |
Maintenance free lead-acid batteries
/ 12V x 29pcs |
||||
| Maximum Charge Current Adc (Selectable) |
8 |
15 |
20 |
25 |
|
| Battery Start |
Yes, UPS can be started without AC source. |
||||
| INVERTER |
|
||||
| Output Voltage |
190V /208V /220V / 380V / 400V /415V /440V /480V / 600V, 3P4W or 3P3W |
||||
| Wave Form |
Sine Wave |
||||
| Output Power Factor |
0.8 |
||||
| Frequency Lock Range |
50 / 60 Hz + / - 3Hz |
||||
| Output Frequency (Free Running) |
50 / 60 Hz + / - 0.1 Hz |
||||
| Phase Shift Under 100%
Unbalance Load |
< 0.5° |
||||
| THD (Linear Load) |
< 2 % |
||||
| Overload |
<110% |
Continuous |
|||
| 110 - 125% |
15 minutes |
||||
| 125 - 150% |
10 minutes |
||||
| > 150% |
1 minute |
||||
| Efficiency (100% Load) |
93% |
93% |
93.5% |
93.5% |
|
| STATIC SWITCH |
|
||||
| Voltage Range |
173-277 VAC (L-N) |
||||
| Mains ???u Inverter |
0 ms |
||||
| OVERALL CHARACTERISTICS |
|
||||
| Overall Efficiency |
91% |
91% |
91.5% |
92% |
|
| Maximum Heat Dissipation (Kw) |
1.1 |
1.9 |
2.6 |
3 |
|
| Height x Width x Depth
(mm) |
1600 x 550 x 800 |
||||
| Weight (Kg, without battery) |
300 |
400 |
480 |
550 |
|
| Audible Noise |
< 65 dBA (At 1 M) |
||||
| Temperature |
0 – 40℃ ( 32 – 104℉ ) |
||||
| Humidity |
0% - 90% (NonLCCondensing) |
||||
| Altitude |
<1500 M Above Sea Level |
||||
| EN50091-1,-2 |
YES |
||||
| Short Circuit Pretection |
YES |
||||
| Lightning / EMC Filter |
MOV / Input&Output (FCC CLASS A) |
||||
| Galvanic Isolation |
Input&Output true Galvanic isolation |
||||
| LED,LCD,Buzzer |
YES |
||||
| Remote Control / Communication Interface |
Monitoring 1~99 UPS simultaneously /
Dry contact, RS232, RS485 |
||||
| . Different specifications required are available. . All specifications mentioned above are subject to change without prior notice. |
|||||
| Copyright © 2003-2007 常陽興業股份有限公司. soltec@soltec.com.tw |