Converter AHA-653-FC(6.5KVA)
Features
- Adopting the DSP technology and IGBT component.
- Wild AC input range (145~315VAC),Wild frequency input range.
- Special load protection makes UPS is fit for any type of the load.
- Startup without surge current.
- AC/DC input with two sources.
- Powerful overload and interference-resist ability.
- The Galvanic Isolation in AC input and output.
- The design of anthropomorphized operation makes the operation more safe and convenient.
- The design of single PC control can improve the reliability and maintenance conveniently.
- Perfect protection ensures the system can automatically cut off when the abnormal condition occurred.
- Repair & Maintenance the whole day through Long-range dial
- Intelligent communication function supports the MAGATEC, UPSilon2000 and Netagent.
- Approve EN50091-1,-2
Overview
The Vesta series provides comprehensive protection and high power density in small and economic package. Compared to traditional UPS towers of the same size, Vesta UPS is more compact and offers greater comprehensive power protection against surges and spikes. Equipped with a voltage stabilizer, this UPS will continue providing clean and stable power to connected equipment while its embedded microprocessor controller guarantees high reliability, perfect for any home or small office applicatio
|
Capacity |
6.5KVA |
Input |
Voltage |
single phase 220Vac -20% +35% |
Frequency |
50Hz or 60Hz +/- 5% |
Output |
Voltage |
single phase 220Vac +/- 5% (adjustable) |
Frequency |
50Hz or 60Hz, 400Hz (option) +/- 0.5% |
Voltage Regulation |
+/- 1% |
Frequency Stability |
+/- 0.5% (Free Running) |
Transient Response |
+/- 3% (100% load variation) |
Waveform |
Sinewave THD < 3% at 0-100% linear load |
Overload Capacity |
120% load 30 seconds, >150% constant power. |
Power factor |
0.7-1, lag |
Crest ratio |
3 : 1 |
Efficiency |
AC to AC |
>85% |
Protection |
Overload |
125% 30sec. |
Short Circuit |
Current Limited and cut-off and fuse and breaker |
EMI/EMC |
EN50091-2, CE Approved |
Audible Alarm |
Mains Failure |
Sounding every four seconds after mains fail, 90 seconds mute |
Final Discharge |
Sounding once every second as battery approaches |
Overload |
Continuously |
Indicator |
LCD |
I/P&O/P voltage, I/P&O/P frequency, Loading %, History record |
LED |
Utility LED (green), Inverter LED (green),
Fault LED (red), Overload (yellow) |
Interface |
Contact Closure |
Support MEGATEC RUPS UPS monitoring software |
RS-232 |
Support MEGATEC RUPSII / UPSilon 2000 monitoring software |
Environment |
Operation Temperature |
0-40 degree C; 32-104 degree F |
Relative Humidity |
20-90% non-condensing |
Audible Noise |
Less than 45dB(at 1 meter) |
Physical |
Net Weigh (KGS/LBs) |
94 kgs w/o battery |
Dimension (WxHxD)mm |
480 x 845 x 340 |
* Specifications are subjected to change without prior notice. |
|