ProdcutLines

  • Options

Converter AHA-503-FC(5KVA)

big_pic

Features

  • Adopting the DSP technology and IGBT component.
  • Wild AC input range (145~315VAC),Wild frequency input range.
  • Special load protection makes UPS is fit for any type of the load.
  • Startup without surge current.
  • AC/DC input with two sources.
  • Powerful overload and interference-resist ability.
  • The Galvanic Isolation in AC input and output.
  • The design of anthropomorphized operation makes the operation more safe and convenient.
  • The design of single PC control can improve the reliability and maintenance conveniently.
  • Perfect protection ensures the system can automatically cut off when the abnormal condition occurred.
  • Repair & Maintenance the whole day through Long-range dial
  • Intelligent communication function supports the MAGATEC, UPSilon2000 and Netagent.
  • Approve EN50091-1,-2

Overview

The Vesta series provides comprehensive protection and high power density in small and economic package. Compared to traditional UPS towers of the same size, Vesta UPS is more compact and offers greater comprehensive power protection against surges and spikes. Equipped with a voltage stabilizer, this UPS will continue providing clean and stable power to connected equipment while its embedded microprocessor controller guarantees high reliability, perfect for any home or small office applicatio
Specifications

Capacity

5KVA

Input

Voltage

single phase 220Vac -20% +35%

Frequency

50Hz or 60Hz +/- 5%

Output

Voltage

single phase 220Vac +/- 5% (adjustable)

Frequency

50Hz or 60Hz, 400 Hz (option) +/- 0.5%

Voltage Regulation

+/- 1%

Frequency Stability

+/- 0.5% (Free Running)

Transient Response

+/- 3% (100% load variation)

Waveform

Sinewave THD < 3% at 0-100% linear load

Overload Capacity

120% load 30 seconds, >150% constant power.

Power factor

0.7-1, lag

Crest ratio

3 : 1

Efficiency

AC to AC

>85%

Protection

Overload

150% 30sec.

Short Circuit

Current Limited and cut-off and fuse and breaker

EMI/EMC

EN50091-2, CE Approved

Audible Alarm

Mains Failure

Sounding every four seconds after mains fail, 90 seconds mute

Overload

Continuously

Indicator

LCD

I/P&O/P voltage, I/P&O/P frequency,
Loading %, History record

LED

Utility LED (green), Inverter LED (green),
Fault LED (red), Overload (yellow)

Interface

Contact Closure

Support MEGATEC RUPS UPS monitoring software

RS-232

Support MEGATEC RUPSII / UPSilon 2000 monitoring software

Environment

Operation Temperature

0-40 degree C; 32-104 degree F

Relative Humidity

20-90% non-condensing

Audible Noise

Less than 45dB(at 1 meter)

Physical

Net Weight (KGS/LBs)

66 kgs w/o battery

Dimension (WxHxD)mm

230 x 685 x 578

* Specifications are subjected to change without prior notice.